Global parameters can be viewed and / or edited by selecting
CCEX à
Configure à
CCEX Global. The last step can be done alternatively by pressing the Configure
CCEX button in the main window.
| PARAMETER |
DESCRIPTION |
| Manager
Status |
Enables or disables all CCEX activities. When
Enabled, any enabled sub processes are allowed to execute. When Disabled
no automatic activities are allowed to execute. |
| Management Method |
Parameter value determines on what level CCEX
does capacitor control. Possible values are By Feeders, By
Substations, and Global. |
| Control Parameter |
Determines which parameter is to be used as
the control parameter for doing capacitor control. Possible values are Reactive
Power, Power Factor, and NONE. In the latter case CCEX
is essentially turned off, but manual capacitor control is still
possible. |
| Connect Threshold |
Parameter specifies at which value of control
parameter CCEX must connect capacitor bank(s) to the power grid. |
| Disconnect Threshold |
Parameter specifies at which value of control
parameter CCEX must disconnect capacitor bank(s) from the power
grid. |
| RUEX Replication Period (Seconds) |
Parameter specifies how often CCEX checks on
RUEX for new data. When new data is available CCEX replicated the data
for its own use. |
| Demand Units of Measure |
Units of measure (kW, MW, etc.) used for
recording and display purposes. |
| Reactive Power Units of Measure |
Units of measure (VAr, kVAr, etc.) used for
recording and display purposes. |
| Number of Readings |
Parameter specifies number of historical
control parameter readings to hold for global control parameter trending displays. |
| Alarms |
Can be Enabled or Disabled. When
Enabled
visual and audio alarms are generated in addition to alarm log entries
when error conditions occur. When Disabled, log entries are generated
only. |
| Management Cycle Logs |
When Enabled CCEX generates one line
event log entry for each global management cycle, reporting
demand, reactive power, power factor, number of capacitors connected to
the power grid, etc. |
| Capacitor Operation Logs |
Specifies which capacitor operations are
recorded in CCEX event log file. The following options are available:
All - Every control code is recorded; State Changes Only - Only control
codes which cause state change (OnàOff
and OffàOn)
are recorded; None - recording is disabled. Note that this parameter
does not affect NTMCRDR capacitor
activity recording. The latter always records control point
state changes only. |
| NTMC Resident Data Recording Status |
CCEX records global demand, reactive power,
and power factor into its NTMCRDR
files when this parameter is Enabled. |
| NTMCRDR
File Size (kB) |
Size limit of global NTMCRDR
files. Unlike
event log files which are circular, data recording files are not. An
alarm is generated every time new data is appended to a data recording
file which is larger than allowed by this parameter. No data is lost,
however alarms persist. The only way to get rid of alarms is to archive
the file. |
| NTMCRDR
File Backup Directory |
Specifies the directory where CCEX NTMCRDR
files get archived. This can be a directory on a local hard disk, or a
network drive. |
| Auto -
Archiving (Data and Event Log Files) |
Specifies if data recording files and event
log file are to be archived automatically, and how often. Possible
options are Disabled, Daily, Weekly, and Monthly. |
Global Dates and Times parameters can be viewed and / or edited by selecting
CCEX à
Configure à
Global Dates and Times:
| PARAMETER |
DESCRIPTION |
| Weekday Management |
One parameter for each Weekday (Monday,
Tuesday, ...). When Enabled, automatic management is allowed
that day of the week. This parameter overrides all less restrictive
lower level weekday parameters. |
| Start
Management Time of Day |
Global start time, specifying the time of day
when automatic management functions can execute. This parameter
overrides less restrictive lower level parameters. |
| Stop Management Time of Day |
Global end time, specifying the time of day
when automatic management functions cease to execute. Any capacitors
connected to the grid are disconnected from it at this time. This
parameter overrides less restrictive lower level parameters. |
| Management Period (RUEX Polling Cycles) |
Parameter specifies how often, in terms of
RUEX polling cycles, CCEX is supposed to manage capacitor banks. |
Capacitor State Reinserting parameters can be viewed and / or edited by selecting
CCEX à
Configure à
Capacitor State Reinserting:
| PARAMETER |
DESCRIPTION |
| Capacitor State Reinserting |
Enables or disables capacitor state
reinserting. |
| Reinserting Period (sec.) |
Parameter specifies how often capacitor state
reinserting manager is to send out reinsertion codes. |
External Commands parameters can be viewed and / or edited by selecting
CCEX à
Configure à
External Commands:
| PARAMETER |
DESCRIPTION |
| External
Command Processing |
Enables or disables processing of command requests
generated via the internet. |
| Max.
age of External Command (Minutes) |
Specifies maximum age of external commands,
in minutes. Command requests older than specified here are not executed. |
Substations
Substation parameters can be viewed and / or edited by first opening
the substation window, then executing the Substation à
Configure command, or by pressing the Configure Substation button
in the substation window.
| PARAMETER |
DESCRIPTION |
| Substation Id |
Specifies substation identifier. |
| Manager Status |
Enables or disables all substation activities. When
Enabled, any enabled substation sub processes are allowed to execute. When
Disabled
no substation automatic activities are allowed to execute. |
| Contribution to Global |
When Enabled, control parameter value total for this
substation is added to system total. |
| Connect Threshold |
Parameter specifies at which value of control
parameter CCEX must connect capacitor bank(s) to the power grid. |
| Disconnect Threshold |
Parameter specifies at which value of control
parameter CCEX must disconnect capacitor bank(s) from the power
grid. |
| Number of Readings |
Parameter specifies number of historical readings to hold for
substation control parameter trending displays. |
| Management Cycle Logs |
When Enabled CCEX generates one line
event log entry for each substation management cycle, reporting
demand, reactive power, power factor, number of capacitors connected to
the power grid, etc. |
| NTMC Resident Data Recording Status |
CCEX records substation demand, reactive
power, and power factor into its NTMCRDR
files when this parameter is Enabled. |
| NTMCRDR
File Size (kB) |
Size limit of substation NTMCRDR
files. Unlike
event log files which are circular, data recording files are not. An
alarm is generated every time new data is appended to a data recording
file which is larger than allowed by this parameter. No data is lost,
however alarms persist. The only way to get rid of alarms is to archive
the file. |
Feeders
Feeder parameters can be viewed and / or edited by first opening
the Feeder window. This can be done by first opening a substation window, and
executing the Substation à
View Feeder List command (or by pressing the Substation Feeders button
in the substation window) to open the substation feeder list. One then select
a feeder from the feeder list. Lastly, execute Feeder à
Configure command, or press the Configure On-line Feeder button
in the feeder window.
| PARAMETER |
DESCRIPTION |
| Feeder Id |
Specifies feeder identifier. |
| Manager Status |
Enables or disables all feeder activities. When
Enabled, all enabled feeder processes are allowed to execute. When
Disabled
no feeder automatic activities are allowed to execute. |
| Connect Threshold |
Parameter specifies at which value of control
parameter CCEX must connect capacitor bank(s) to the power grid. |
| Disconnect Threshold |
Parameter specifies at which value of control
parameter CCEX must disconnect capacitor bank(s) from the power
grid. |
| Default Demand |
Last valid demand reading obtained from RUEX.
When valid demand reading is not available, this value is used until manually
changed, or until another valid reading arrives. |
| Demand Reactive Power |
Last valid reactive power reading obtained
from RUEX. When valid reactive power reading is not available, this
value is used until manually changed, or until another valid reading
arrives. |
| Default Power Factor |
Power factor is computed from Default
Demand and Demand Reactive Power for every management cycle. |
| Contribution to Substation |
When Enabled, control parameter value total for this
feeder is added to owner substation total. |
| Connect Priority (1 = Highest) |
Parameter sets connect priority for all
capacitor banks on this feeder. This way capacitors on one feeder can be
prioritized ahead of all capacitors on another feeder. |
| Disconnect Priority (1 = Highest) |
Parameter sets disconnect priority for all
capacitor banks on this feeder. This way capacitors on one feeder can be
prioritized ahead of all capacitors on another feeder. |
| Remote Unit Domain |
Identifier of RUEX domain
owning remote unit used for importing demand and reactive power from
RUEX. |
| Remote Unit |
Identifier of remote unit
used for importing demand and reactive power from RUEX. |
| Demand Analog Point |
Identifier of analog
point used to import demand from RUEX. |
| Reactive Power Analog Point |
Identifier of analog
point used to import reactive power from RUEX. |
| Number of Readings |
Parameter specifies number of historical readings to hold for
feeder control parameter trending displays. |
| Management Cycle Logs |
When Enabled CCEX generates one line
event log entry for each feeder management cycle, reporting
demand, reactive power, power factor, number of capacitors connected to
the power grid, etc. |
| NTMC Resident Data Recording Status |
CCEX records feeder demand, reactive
power, and power factor into its NTMCRDR
files when this parameter is Enabled. |
| NTMCRDR
File Size (kB) |
Size limit of feeder NTMCRDR
files. Unlike
event log files which are circular, data recording files are not. An
alarm is generated every time new data is appended to a data recording
file which is larger than allowed by this parameter. No data is lost,
however alarms persist. The only way to get rid of alarms is to archive
the file. |
Capacitors
Capacitor bank parameters can be viewed and / or edited by first opening
the Feeder window. This can be done by first opening a substation window, and
executing the Substation à
View Feeder List command (or by pressing the Substation Feeders button
in the substation window) to open the substation feeder list. One then select
a feeder from the feeder list. Next press the Feeder Capacitors button
to open the capacitor list window. Lastly, right-click onto the capacitor of
choice, and select the Configure command from the context menu.
| PARAMETER |
DESCRIPTION |
| Capacitor Id |
Specifies capacitor identifier. |
| Manager Status |
Enables or disables all automatic capacitor activities. When
Enabled, all enabled capacitor processes are allowed to execute. When
Disabled
no capacitor automatic activities are allowed to execute. |
| Operation Mode |
Parameter specifies capacitor operation mode.
When set to Auto, capacitor bank is allowed to be included in
automatic operations. When set to Manual, CCEX does not operate
the bank unless a manual command is issued by the operator. |
| Reactive Power Rating |
Parameter value specifies reactive power rating of the
capacitor bank. The value must be in the same units as the units used by
feeders. |
| Connect Priority (1 = Highest) |
Parameter sets connect capacitor bank
priority within the feeder. |
| Disconnect Priority (1 = Highest) |
Parameter sets disconnect capacitor bank
priority within the feeder. |
| Remote Unit Domain |
Identifier of RUEX domain
owning remote unit used for control of the capacitor bank. |
| Remote Unit |
Identifier of remote unit
used for control of the capacitor bank. |
| Control Point |
Identifier of control
point used for control of the capacitor bank. |
| Schedule |
Schedule identifier assigned to this
capacitor bank. |
| Capacitor Type (Primary / Secondary) |
Specifies the type of capacitor. When set to Primary,
the capacitor bank is analogous to a primary
capacitor. When set to Secondary, the capacitor bank is analogous
to a secondary
one, and must be associated with a primary capacitor bank. Also, the Reactive
Power Rating must be set to 0. |
| Primary Capacitor Substation Id |
Parameter specifies the substation which
owns this capacitor's associated primary capacitor. This parameter is ignored if the
Capacitor Type
parameter is set to Primary. |
| Primary Capacitor Substation Id |
Parameter specifies the feeder which
owns this capacitor's associated primary capacitor. This parameter is ignored if the
Capacitor Type
parameter is set to Primary. |
| Primary Capacitor Id |
Identifies the associated primary capacitor id. This parameter is ignored if the
Capacitor Type
parameter is set to Primary. |
Schedules
Schedule parameters can be viewed and / or edited by first selecting Schedule à
View Schedule List command, then right clicking onto the schedule of
choice, and selecting Configure command.
| PARAMETER |
DESCRIPTION |
| Schedule Id |
Specifies the schedule identifier. |
| Manager Status |
Enables or disables all capacitors
associated with this schedule. When
Enabled, capacitor related automatic activities execute. |
| Weekday Management |
One parameter for each Weekday (Monday,
Tuesday, ...). When Enabled, automatic management is allowed
that day of the week for capacitors on this schedule. |
| Start Management Time of Day |
Specifies the time of day
when automatic management functions can execute using capacitors on this
schedule. |
| Stop Management Time of Day |
Specifies the time of day
when automatic management functions using capacitors on this
schedule cease to execute. Any capacitors connected to the grid are
disconnected at this time. |
| Max. Number of Connected Capacitors |
Specifies maximum number of capacitors on this
schedule that are allowed to be ON simultaneously at any one time. |
| Max. Connects per Day |
Specifies maximum number any capacitor on this
schedule is allowed to be turned ON (connected) in any given day. |
| Max. Capacitor Accumulated Connected Time (Sec) |
Specifies the maximum allowed time in ON state, in seconds, any
capacitor on this schedule is allowed to accumulate. |
|