|
Database
Metering Points
One must first define, configure,
and put on-line one or more metering
points.
Schedules
The next step is to define the schedules.
Each schedule needs to be defined, configured,
and put on-line.
Demand Points
To build a list of demand
points, one needs to define each demand
point, configure it, and put
it on-line by adding it to one of the metering points.
Each demand point must be mapped to an analog point,
which can be done by appropriately specifying RUEX domain,
remote unit, and analog
point identifiers.
Load Points
To build a list of load
points, one needs to define each load
point, configure it, and put
it on-line by adding it to one of the metering points.
Each load point must be mapped to a control
point, which can be done by appropriately specifying RUEX domain,
remote unit, and control
point identifiers.
If associated RUEX remote unit has two-way capabilities, and there is a
counter available on that remote unit, the load point must also be mapped
to that counter. The latter assignment can be left as NONE if
two-way load management is not going to be performed.
Each load point must also be mapped to an appropriate schedule,
or schedules, if multiple load management strategies are going to be
executed.
Data Processing
RUEX analog point thresholds
must be defined (high threshold must be larger than low threshold),
otherwise LMEX does not accept analog point values as valid. LMEX also rejects any values
outside the range defined by the thresholds.
Each demand point must be configured
to either add or subtract its value to the owner metering point demand total
value. That same parameter can also be set so no contribution is made to the
metering point total.
Each metering point must be configured
to either add or not add its value to the system demand total value.
Data Recording
To record system total demand, one must enable
LMEX NTMCRDR.
To record metering point total demand, one must enable
metering point NTMCRDR.
To record demand point total demand, one must enable
demand point NTMCRDR.
To record load point activity, one must enable
corresponding RUEX control point NTMCRDR. In addition, RUEX records
control point activity into RUEX event log file. See documentation on RUEX Control Point Operation Logging
parameter.
To generate system total load management cycle logs, one must enable
Load Management Cycle Logs parameter.
To generate metering point load management cycle logs, one must enable
metering point Load Management Cycle Logs parameter. To get individual
demand input resolution one must set this parameter to MPT and Demands.
Data Archiving
One has to periodically archive data and event logs. Both operations are
manually initiated by the operator.
Data archiving is initiated by executing the LMEX Archive
Data Recording Files command. The accumulating data files get appended to
the corresponding archives located in the NTMCRDR
archive directory.
Event log archiving is initiated by executing the LMEX Archive
Event Log File command. The accumulating event log file gets copied to the
NTMC event log archive directory, common to all NTMC
components, and reset to empty.
Data recording files and event log file can be periodically
archived automatically if so desired. Care must be taken that archive
directory is always available and in the same place, otherwise archives are
scattered in different locations, and historical searches become inconvenient.
Billing Periods
To distinguish between peak and off-peak billing periods, peak billing
period start and end
times of day must be defined.
Furthermore, global
weekday management must be enabled on the day of the week for peak billing
period to be in effect that day.
In addition, when load management
waiver is in effect, off-peak billing period is in effect.
By definition, when peak period is not in effect, off-peak period is in
effect.
MCDA LMEX
billing period data filtering can be performed when analyzing NTMCRDR
and RURDR data.
One-way Load Management
In all cases
- Load management must be enabled.
- Global weekday
management must be enabled on the day of the week load management is
to be performed.
- Global start and stop
management times of day must be defined properly. In order to be
effective, any lower level start and stop times (such as schedules) must
be at least as restrictive, or more restrictive than the global start and
stop times mentioned above.
- Pre-management time must be defined if initial shed is to begin before
above start management time of day. This is used when control code
dispatcher uses substantial amount of time to dispatch control codes due
to low communication speeds.
- If RUEX polling period is to be controlled dynamically, Dynamic RUEX Polling Period Control
must be enabled. See also documentation on this parameter regarding RUEX
setup.
- Active Cycle Demand Correction
should be enabled.
- Shed Ramping Rate, Restore
Ramping Rate, and High Threshold Overruns to Reset
parameters can be set if desired.
- All metering points involved in load management must be enabled.
- All metering points involved in load management must have Load Rating Bias Factor
parameter defined properly. If, for example, it seems that, on the
average, only 75% of the loads are running at any one time, the value of
this parameter should be set to 75.
- All demand points involved in load management must be enabled.
- All demand points involved in load management must have the Contribution to Metering Point
parameter defined appropriately.
- All load points involved in automatic load operations must be enabled,
and in Auto mode.
Similarly for the associated RUEX control points - they must be enabled
and in Auto
mode.
- All load points involved in automatic load management must have the Load Type,
Primary Load Metering Point,
and Primary Load Id
parameters defined appropriately. The latter two are ignored when the Load
Type parameter is set to Primary.
- All three load point schedule assignments (Primary
Strategy, Secondary Strategy,
and Emergency Strategy) should
be pointing to the same schedule.
- All schedules involved in load management must be enabled.
- Schedule weekday
management must be enabled on the day of the week load management is
to be performed, otherwise loads assigned to the schedule are kept in the
ON state (connected to the power grid).
- Schedule start and
stop
management times of day must be defined properly. Load points assigned to
the schedule are kept in the ON state (connected to the power grid) during
times of day which fall before the start time, or after the stop time
defined in the schedule. Careful: if the time window defined here has no
overlap with the global time window (global start and stop time of day
described above), loads assigned to the schedule will never be
disconnected from the power grid.
- Load Shed Priority and Load
Restore Priority parameters can be defined to control load operation
priorities. Load point shed priority is determined as follows:
- Schedule shed priority - parameter defined in the schedule, the
lower the value, the higher the priority.
- Load activity. Active load has higher priority to be
disconnected. Activity rate is immaterial, LMEX only considers
activity vs. no activity. Otherwise active loads would be turned off
more frequently.
- Number of times load was turned off in a day. Loads which have been
disconnected fewer times have higher priority. Numbers are reset at
midnight.
- Load point Accumulated Off Time (AOT) - the lower the value, the
higher the priority.
Load point restore priority is determined as follows:
- Schedule restore priority - parameter defined in the schedule, the
lower the value, the higher the priority.
- Load point Accumulated Off Time (AOT) - the lower the value, the
higher the priority.
- Max. Number of Loads Off, Max. Sheds per Day,
Max. Failed Operations
per
Day, and Max. Load Accumulated Time Off
parameters may have to be defined to impose the various limits defined by the
parameters.
Global load management:
- Global Demand
Management Method parameter must be set to Global.
- High and low
demand thresholds must be specified. The former must be greater than the
latter, and they must not be too close together in order to prevent system
demand oscillations. LMEX sheds load when it exceeds the high threshold,
it attempts to bring it under the high threshold. LMEX attempts to restore
load when it falls below the low threshold, it tries to restore enough
loads to bring the load just below the high threshold.
- All metering points involved in load management must have their Demand Management Method
parameter set to Global.
Metering Point load management:
- Global Demand
Management Method parameter must be set to Metering Point.
- Metering point High and
low
demand thresholds must be specified. The former must be greater than the
latter, and they must not be too close together in order to prevent
metering point demand oscillations. LMEX sheds metering point load when it exceeds the high threshold,
it attempts to bring it under the high threshold. LMEX attempts to restore
metering point load when it falls below the low threshold, it tries to restore enough
loads to bring the load just below the high threshold.
- All metering points involved in load management must have their Demand Management Method
parameter set to By Metering point.
- High Threshold Overruns to Reset
parameter may be defined if dynamic high threshold control is desired.
Two-way Load Management
In addition to one-way load management parameters (above), the following
must be defined:
- Two-Way Load Management
parameter must be Enabled.
- All metering points involved in load management must have Load Rating Bias Factor
parameter set to 100.
- All metering points involved in load management must have Load Pulse Threshold Bias Factor
defined properly. The value must be 100 or less, depending on the remote
unit model used, and configuration of that remote unit.
- Each load point involved in load management must have Energy Per Pulse
parameter properly defined. Same units of measure as those in load Power
Rating parameter must be used.
Any parameter documentation in this section, which is in contradiction to
that defined in the One-way Load Management section, takes precedence over
that defined in the One-way Load Management section.
Strategy Based Load Management
In addition to one-way or two-way load management parameters (above), the
following must be defined:
- If Strategy
Selection Method parameter (above) is set to Global, LMEX Strategy
parameter must be properly defined.
- If Strategy
Selection Method parameter (above) is set to Metering Point,
every metering point must have the following parameters properly defined
as follows:
- If Load Management Strategy Selection Method
parameter is set to Manual, Load
Management Strategy In Effect parameter must be defined. The latter
determines load management strategy in effect.
- If Load Management Strategy Selection Method
parameter is set to Time of Day, Primary Load Management Strategy Start Time
of Day and Secondary
Load Management Strategy Start Time
of Day parameters must be defined. Strategy in effect is thus
depends on the time of day.
- If Load Management Strategy Selection Method
parameter is set to Demand, Demand High Threshold
and Demand Low Threshold
parameters must be defined. Strategy in effect thus depends on metering
point load.
- All three load point schedule assignments (Primary
Strategy, Secondary Strategy,
and Emergency Strategy) should
be pointing to appropriately defined schedules.
- Every schedule must have Load
Control Authority parameter properly defined.
- When above parameter is set to Demand Management Algorithm, every
schedule Load Control
Factor parameter must be defined.
Any parameter documentation in this section, which is in contradiction to
that defined in the One-way Load Management section, takes precedence over
that defined in the One-way Load Management section.
Load Rotation
For load rotation to work, load rotation manager must be Enabled.
In addition, every schedule involved in load rotation must have the Load
Rotation Period parameter set to a positive value. Load
Control Authority and Load Control
Factor parameters must also be defined properly.
Load State Reinserting
For Load State Reinserting to work, LSR manager must be Enabled.
Reinserting Time of Day
parameter must be defined to specify the time of day when reinsertion codes
are to be transmitted, or Reinserting
After Peak Period parameter must be defined to specify how long after peak
billing period expires reinsertion codes are to be transmitted.
If the parameter is defined more than once, the codes
go out several times per day. For each time of day the Reinserting Method
parameter must be defined so LMEX knows which control codes to send out.
Load Pre-polling
For load pre-polling to work, LMEX Load
Pre-polling parameter must be Enabled. Pre-polling Pass 1
and Pre-polling Pass 2
parameters must be defined. Every load to be pre-polled must have the Pulse Counter
parameter defined, pointing to a valid RUEX pulse counter
residing on the same RUEX remote
unit as the control point
used to operate the load.
For NTMC systems which include MREX, the automated meter reading component,
one latest meter reading operation can serve as one pre-poll, as long as MREX
meters are mapped to the same pulse counters as the above described loads.
Furthermore, only one pre-polling pass can be used if desired. One
advantage using two pre-polling passes is to have more recent data. One
disadvantage of pre-polling twice is that the system takes more time polling
for data. The latter can take substantial amounts of time on systems limited
by slower baud rates, such as systems using radio communications.
Load Point Operation Modes
Put the load in AUTO or
MANUAL mode. Frozen mode comes about from operating the load manually via the
web.
Load Management Waivers
To waive load management for part of the day, first define Load Management Waiver Start Time of Day
and Load Management Waiver End Time of Day
parameters, then set the Load Management Waiver
parameter to Enabled. The latter parameter gets set to Disabled
automatically the next midnight.
These parameters can be manipulated externally via communications channel
of choice. Custom protocols are available upon request.
To receive waiver notification messages via a modem, Nebraska
Public Power District customers in the state of Nebraska must set up a
dedicated telephone line, a modem, then set up one NPPD type IOEX
application client and one NPPD type IOEX
application server using that telephone line and the modem. The server has
to be enabled and properly configured with correct addresses - see
documentation on IOEX NPPD
type servers.
Secondary Load Points
To define a load point a secondary load point, the Load
Type parameter must be set to Secondary, Primary
Load Metering Point parameter must identify the metering point which
contains the primary load point, and Primary
Load Id parameter must identify that primary load point.
Multiple secondary loads can be assigned the same primary load point. When
the latter changes state, all associated secondary load points are sent
corresponding control codes or notifications.
The following rules must be observed when defining secondary loads:
- All secondary loads must be assigned to a schedule which is completely
unrestricted, i.e. enabled, available every day of the week, at all times
of day.
- Each secondary load must be assigned zero power
rating.
Twin Load Points
To define a load point a twin load point, the load point must first be
defined as secondary (see above). The corresponding primary load point must then
identify this secondary load point as a twin load point. There can only be one
twin load point for every primary load. The following primary load point
parameters must identify the twin load:
- Twin Load Metering Point Id
- Twin Load Id
If twin load so identified is not a secondary load, it does not operate as a
twin load. Twin loads must be secondary loads to prevent the scenario where
automatic load management first operates a twin load, without operating
associated primary load point.
|