Configuration

Home ] Up ]

 

MREX

Global parameters can be viewed and / or edited by selecting the MREX à Configure command. The last step can be done alternatively by pressing the Configure MREX button in the main window.

PARAMETER DESCRIPTION
Manager Status Enables or disables all MREX activities. When Enabled, any enabled sub processes are allowed to execute. When Disabled no automatic activities are allowed to execute.
Alarms Can be Enabled or Disabled. When Enabled visual and audio alarms are generated in addition to alarm log entries when error conditions occur. When Disabled, log entries are generated only.
Units of Measure Parameter specifies units of measure (e.g. kWh) used for displays and reports.
RUEX Polling Period (sec.) Parameter specifies how often, in seconds, MREX checks up RUEX for any changes in RUEX database.
Export File Directory Parameter specifies the directory for data and report export files. 
Export Meters Parameter identifies which group of meters is to be selected for billing data exports. When set to All, all meter data get exported. When set to By Monthly Schedule, only meters assigned to a selected monthly schedule (see below) are exported.
Export Meters On Monthly Schedule Parameter specifies the monthly schedule assigned to meters whose billing data are to be exported. This parameter is considered only when the Export Meters parameter (above) is set to By Monthly Schedule.
Billing Archive Scanning Billing data exports can be done on archived data files when this parameter is set to Enabled. Archive files are ignored when this parameter is Disabled.
Billing Scan Start Date and Time This parameter defines the start date and time when Billing Archive Scanning is Enabled. The filter will reject any data with time stamps prior to the date and time set here.
Billing Scan End Date and Time This parameter defines the end date and time when Billing Archive Scanning is Enabled. The filter will reject any data with time stamps more recent than the date and time set here.
Data Rec. Interval (Minutes - For Reports) Parameter specifies (must match) the data recording interval for the data being studied. The value does not affect the RURDR data recording interval done by MREX. The value is used for report calculations only.
<Day of Week> Billing Period Specifies how billing period is determined for the current day of the week. When set to Off-peak, billing period is off-peak all that day. When set to Time Of Day, parameters Peak Billing Period Start Time of Day, and Peak Billing Period End Time of Day (below) specify start and end times of day for the peak belling period.
Peak Billing Period Start Time of Day Parameter specifies time of day when peak billing period starts. This information is used in RURDR files and billing data exports.
Peak Billing Period End Time of Day Parameter specifies time of day when peak billing period ends. This information is used in RURDR files and billing data exports.
Y Axis Filtering This parameter must be Enabled for Y-Axis filtering to work. The latter does not work when this parameter is Disabled.
Y Lowest This parameter defines the lowest data value accepted in billing data exports when Y Axis Filtering (above) is Enabled. The filter will reject any data with values lower than the one  specified here.
Y Highest This parameter defines the highest data value accepted in billing data exports when Y Axis Filtering (above) is Enabled. The filter will reject any data with values higher than the one  specified here.
NTMCRDR File Backup Directory Specifies the directory where MREX NTMCRDR files get archived. This can be a directory on a local hard disk, or a network drive.
External Command Processing Enables or disables processing of command requests generated via the internet.
Max. age of External Command (Minutes) Specifies maximum age of external commands, in minutes. Command requests older than specified here are not executed.
Auto - Archiving (Data and Event Log Files) Specifies if data recording files and event log file are to be archived automatically, and how often. Possible options are Disabled, Daily, Weekly, and Monthly.

 

Meters

To display a meter,  first display the on-line meter list, then click on the meter of interest.

Meter parameters can be viewed and / or edited by selecting the Meter à Configure menu. The last step can be done alternatively by pressing the Configure On-line Meter button in the meter window.

PARAMETER DESCRIPTION
Meter Id Specifies meter identifier. 
Manager Status Enables or disables all meter activities. When Enabled, the meter is included in all automatic MREX activities. When Disabled, the meter is excluded from those activities, however it can still be manipulated manually.
Meter Number Meter number. Used for book keeping, search, and retrieval purposes.
Account Number Account number. Used for book keeping, search, and retrieval purposes.
Pulses per Disk Revolution Parameter specifies the number of received pulses per revolution of the meter disk.
Wh per Disk Revolution (Kh) Specifies the number of Watt Hours per revolution of the meter disk. This number is usually printed on meters as Kh.
Number of Digits Parameter specifies the number of dial digits displayed on the meter. 
Dial Reading Multiplication Factor Specifies the dial reading multiplication factor used for the meter.
Remote Unit Domain Specifies RUEX domain which owns the remote unit, and the counter associated with this meter.
Remote Unit Specifies RUEX remote unit which owns the counter associated with this meter.
I/O Point Id Specifies RUEX I/O point associated with this meter, used for reading meter dial values, and NTMCRDR.
RURDR I/O Point Id Specifies RUEX I/O point associated with this meter, used for RURDR. This point may or may not be the same as above, depending on the model of Remote Unit the meter is mapped to. 
Input Type Specifies the type of data input imported via I/O points specified above. Possible options are Analog Reading (I/O points above must be mapped to analog point(s)), or KYZ Pulses (I/O points above must be mapped to pulse counter(s)).
RURDR Type This parameter, used only when 'Input Type' parameter is set to KYZ Pulses, specifies whether to use downloaded counter (rescaled) Values, or (also rescaled) Value Deltas (last reading - previous reading).
Monthly Schedule Specifies the MREX monthly schedule associated with this meter.
NTMC Resident Data Recording Status NTMCRDR is in effect for this meter when Enabled. Not so when  Disabled.
NTMC Resident Data Recording File Size Size limit of meter's NTMCRDR file. Unlike event log files which are circular, data recording files are not. An alarm is generated every time new data is appended to a data recording file which is larger than allowed by this parameter. No data is lost, however alarms persist. The only way to get rid of alarms is to archive the file.

 

Monthly Schedules

To display monthly schedule parameters,  first display the on-line monthly schedule list, right-click on the schedule of interest, then select Configure.

PARAMETER DESCRIPTION
Schedule Id Specifies schedule identifier. 
Manager Status Enables or disables all activities of meters associated with the schedule. When Enabled, the meters are included in all automatic MREX activities. When Disabled, the meters are excluded from those activities, however they can still be manipulated manually.
Activities - Day n One parameter for each day of the month (n = 1, 2, ..., 31). The value can be NONE when no activities are desired for that day, or identifier of the daily schedule specifying activities for that day.

 

Daily Schedules

To display daily schedule parameters,  first display the on-line daily schedule list, right-click on the schedule of interest, then select Configure.

PARAMETER DESCRIPTION
Schedule Id Specifies schedule identifier. 
Manager Status Enables or disables all activities of meters associated with the schedule. When Enabled, the meters are included in all automatic MREX activities. When Disabled, the meters are excluded from those activities, however they can still be manipulated manually.
Non-billing Read Parameter specifies if non-billing read is to be performed on the day of choice (see monthly schedules above). When Enabled, the meters are read, if Disabled they are not.
Non-billing Read Time of Day Specifies the time of day meters are to be read (non-billing read). This parameter is ignored when  the Non-billing Read parameter above is Disabled.
Billing Read Parameter specifies if billing read is to be performed on the day of choice (see monthly schedules above). When Enabled, the meters are read, if Disabled they are not.
Billing Read Time of Day Specifies the time of day meters are to be read (billing read). This parameter is ignored when  the Billing Read parameter above is Disabled.
Data Download Parameter specifies if data download is to be performed on the day of choice (see monthly schedules above). When Enabled, the meter data are downloaded, if Disabled they are not.
Data Download Time of Day Specifies the time of day meter data are to be downloaded. This parameter is ignored when  the Data Download parameter above is Disabled.

 

 